Propane refrigeration loop
Build a refrigeration cycle from saturated liquid propane and work out its coefficient of performance (COP). Introduces vapour fraction specifications.
About 25 minutes. Skills: vapour fraction specs, heater and cooler, compressor, COP. In the app: Start page › Oil & gas exercises › Propane refrigeration loop. The finished case is under Oil & gas starter cases.

1. Start a new case and set up the fluid
Tap New case, add Propane only, keep Peng-Robinson, and tap Simulation.
2. Saturated liquid propane
Material Stream Liquid C3: pressure 245 psia, vapour fraction 0, molar flow 500 lbmole/hr, propane mole fraction 1.0. Leave the temperature empty: it is the boiling point at 245 psia. Any two of temperature, pressure and vapour fraction fix the state.
3. Expansion valve
Valve from Liquid C3 to Flashed C3 at 30 psia. Part of the liquid flashes and the mixture drops to the boiling point at 30 psia.
4. Chiller
Heater named Chiller from Flashed C3 to C3 Vapour, with vapour fraction 1 on C3 Vapour. Its duty is the refrigeration the loop provides.
5. Compressor and condenser
- Compressor from C3 Vapour to Hot C3 at 245 psia.
- Cooler named Condenser from Hot C3 to Condensed C3 with vapour fraction 0.
Condensed C3 should match Liquid C3: the loop closes. It is drawn open, so no Recycle is needed.
6. Questions
- Refrigeration duty. What is the Chiller duty?
- Coefficient of performance. Divide the Chiller duty by the compressor power (in the same units). What is the COP? COP = heat removed ÷ work put in. Colder evaporation or hotter condensing lowers it.
The exercise accepts a COP within 0.03 of your case's value. Btu/hr and hp are different units: convert first, or switch the energy unit (for example with a copied unit set) so both read the same.
Expected results
| Object | Value | Result |
|---|---|---|
| Liquid C3 | Temperature | 120.5 °F |
| Flashed C3 | Temperature | -12.2 °F |
| Flashed C3 | Vapour fraction | 0.4904 |
| Chiller | Duty | 1963131 Btu/hr |
| Hot C3 | Temperature | 163.2 °F |
| K-100 | Power | 490.0 hp |
| Condenser | Duty | 3209797 Btu/hr |
| Loop | COP | 1.57 |
This case agrees with NIST property data for propane to within 2.5 %.
Try next
- Let a spreadsheet calculate the COP for you: see Spreadsheet.
- Lower the valve outlet pressure to 20 psia (colder evaporation) and see the COP fall.
- Continue with Crude oil pipeline.